ProdcutLines

  • Options

On-Line UPS 230V-400V-3-Phase in-3-Phase out-200KVA-500KVA.html

big_pic

Features

  • Advanced technology of PWM, DSP and IGBT switching components Designed to use a high frequency, highly efficiency DSP/IGBT and PWM technology in converting DC to AC power.
  • True Galvanic isolation design Solve ultimately the problem of power system, including noise, lightning, and leakage current etc.
  • Multi-CPU design and software/hardware cooperate control Make the system extremely high reliable.
  • Plug & Play modular design To allow for each power circuit to be easily removed for quick maintenance and troubleshooting.
  • Each phase with individual inverter supporting Characteristics will not be violated under 100% unbalance load.
  • Protection against detaching and floating of the neutral of input power supply Ensure the safety and stability of the UPS power output.
  • Protection from user error Advanced circuitry prohibits damage to the system when the user makes an operational mistake.
  • Intelligent charger with temperature compensation Prolong the battery life expectancy. And with huge charging power (s

Overview

The Vesta series provides comprehensive protection and high power density in small and economic package. Compared to traditional UPS towers of the same size, Vesta UPS is more compact and offers greater comprehensive power protection against surges and spikes. Equipped with a voltage stabilizer, this UPS will continue providing clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability, perfect for any home or small office applicatio
Specifications

KVA

200

240

300

400

500

RECTIFIER

INPUT VOLTAGE

230 / 400 VAC 3 Phase 4 Wire

INPUT RANGE

+/- 15 %

INPUT FREQUENCY

50 / 60 Hz +/- 7%

INPUT POWER FACTOR

0.8

NORMAL INPUT CURRENT(A)

320

384

480

640

800

MAXIMUM INPUT CURRENT(A)

400

480

600

800

1000

POWER WALK IN

15% - 100% : 15 sec

EFFICIENCY

99%

VOLTAGE REGULATION

1%

CURRENT LIMIT(A)

480

576

720

960

1200

RIPPLE VOLTAGE

0.5%

BATTERY

BATTERY TYPE

SEAL LEAD ACID / NiCd

NO. OF CELLS

174 / 271

VOLTAGE RANGE

295 – 410VDC / 285-415VDC

MAXIMUM CHARGE
CURRENT (ADC)

80

96

120

160

200

BATTERY LOW VOLTAGE

320VDC / 305VDC

BATTERY LOW STOP       VOLTAGE

295VDC / 285VDC

BOOST CHARGE

402VDC / 415VDC

FLOAT CHARGE

390VDC / 410VDC

INVERTER

DC INPUT RANGE

285 – 420VDC

WAVE FORM

SINUSOID

OUTPUT VOLTAGE

230 / 400 V 3 Phase 4 Wire

OUTPUT POWER FACTOR

0.8

VOLTAGE REGULATION 100% UNBALANCE LOAD

+ / - 1 %

FREQUENCY LOCK RANGE

45 – 55 Hz / 55 – 65 Hz

OUTPUT FREQUENCY
(FREE RUNNING)

50 / 60 Hz + / - 0.1 Hz

PHASE SHIFT UNDER
100% UNBALANCE LOAD

120 % + / - 0.5∘

THD (LINEAR LOAD)

< 5 %

OVERLOAD

<110%

CONTINUOUS

110 – 125%

15 min

125 – 150%

5 min

> 150%

30 sec

EFFICIENCY(100% LOAD)

95%

95%

95%

95%

95%

MAXIMUM OUTPUT
PEAK CURRENT(A)

834

1000

1252

1670

2087

STATIC SWITCH

VOLTAGE RANGE

173 – 277 VAC (LINE TO NEUTRAL)

FREQUENCY RANGE

45 – 55 Hz / 55 – 65 Hz

EFFICIENCY

99.5%

TRANSFER TIME

- MAINS -> INVERTER

0.2 ms

- INVERTER -> MAINS

0.2 ms

OVERLOAD

100%

30 sec

300%

7 sec

ISOLATION WITH OUTPUT

YES

OVERALL CHARACTERISTICS

OVERALL EFFICIENCY

93%

93%

93%

93%

93%

OPERATING ENVIRONMENT

- TEMPERATURE

0 - 40℃ ( 32 - 104℉ )

- HUMIDITY

0% - 90% ( NON–CONDENSING )

- ALTITUDE

<1500 M ABOVE SEA LEVEL

MAXIMUM HEAT
DISSIPATION(KW)

11.5

13

16.3

23

29

WEIGHT(Kg) (No Battery)

2500

2700

3100

3800

4200

DIMENSION

- HEIGHT(mm)

1600

- WIDTH(mm)

2200

3300

- DEPTH(mm)

800

- AUDIBLE NOISE

< 68 dBA (AT 1 m)

STANDARDS

-EN50091-1,2

YES

-FCC CLASS A

YES

PROTECTIONS

- SHORT CIRCUIT

RECTIFIER, RESERVE, BYPASS NFB

- LIGHTNING

MOV

- EMC FILTER

INPUT & OUTPUT

- GALVANIC ISOLATION

BETWEEN INPUT & OUTPUT

DATA DISPLAY BY LCD

YES

INDICATIONS & ALARMS

- LED,LCD,BUZZER

YES

DRY CONTACT

YES

BATTERY START